Sequence the steps for cold startup of an industrial fire-tube steam boiler after annual inspection and maintenance.
Drag to reorder, or use the arrow buttons.
1Fill boiler to normal water level using treated feedwater and verify on sight glass
2Light burner on low fire and slowly raise temperature (limit 100°F per hour to prevent thermal shock)
3At operating pressure, test each safety valve by raising pressure to pop point
4Complete pre-startup checklist: verify all manways closed, safety devices reinstalled, stack damper open
5Purge firebox with air for minimum 4 furnace volumes per NFPA 85
6Perform bottom blowdown to remove settled sediment, then surface blowdown
7Test low-water cutoff by slowly lowering water level — verify burner lockout
8Transfer boiler to automatic control and verify all safety interlocks are functional