PDU Breaker Sizing per NEC

Data Center Design

Journeyman+60 XP

Scenario

A 42U server rack draws 8 kW of IT load and is fed by a 208V three-phase power distribution unit (PDU). Per NEC Article 210.20, continuous loads must not exceed 80% of the breaker rating. What is the minimum standard breaker size for this rack's branch circuit?